Common questions
Questions practices ask about treatment room electrical
Plain answers to the things practice managers, owners and builders actually type into Google. Can’t find yours? Ask us. In New Zealand? Answers for New Zealand practices.
- What does a new dental surgery need electrically?
A dental surgery is a patient area, so it is wired as a body-protected area to AS/NZS 3003, not like an ordinary office. That means every… - How many power points can a dental surgery have?
There is no cap on the number of outlets in a dental surgery or treatment room. The limit is on the safety switch: one 10 mA RCD can… - Do I need an electrician to move a dental chair?
If moving the chair means moving or adding its electrical supply, yes: that is electrical work in a patient area, and in every state it has… - How often does a medical or dental room need electrical testing?
Body-protected areas have to be inspected and tested at intervals not exceeding 12 months under AS/NZS 3003. In practice that means once a… - What is the green sign in a dental surgery or treatment room?
The green sign tells staff and visiting trades that the room is a body-protected electrical area: its outlets are on 10 mA RCDs and the… - Can a GP consult room be used for ECGs?
Only if it has been set up as a patient area. An ECG connects a mains-powered machine to the patient, which is exactly what body-protected… - Who certifies the electrical work in a dental or medical fit-out?
Your electrician tests the work and issues the certificate your state uses (a Certificate of Electrical Safety in Victoria and the ACT, an… - What is a body-protected electrical area?
A body-protected electrical area is a room wired so that a fault in a piece of medical equipment can’t pass dangerous current through the… - Body-protected vs cardiac-protected: what is the difference?
Both are classifications for patient areas under AS/NZS 3003. Body-protected is for rooms where equipment connects to the body: dental… - What is AS/NZS 3003?
AS/NZS 3003 is the joint Australian and New Zealand standard for electrical installations in patient areas: hospitals, medical and dental… - Why do medical and dental rooms need 10 mA RCDs?
An ordinary safety switch trips at 30 milliamps. A patient connected to equipment, lying down, possibly sedated and with the skin’s… - Does a laser or IPL room need to be body-protected?
Usually, yes. Lasers, IPL, diathermy and electrosurgery are mains-powered equipment applied to the patient, which is the test for a patient… - What happens if the 12-month test on a body-protected area is overdue?
The room doesn’t stop working, which is the problem: nothing visibly changes, but you no longer have evidence that the RCDs trip, the… - Can an existing room be upgraded to a body-protected area?
Yes, and it is a common job: a consult room becoming a treatment room, a new chair going into a room that was storage, a practice taking… - What to ask your electrician before a medical or dental fit-out
Most electricians are good at commercial work and have never wired a patient area. These questions sort that out early, and the answers… - Which rooms count as patient areas? The full list in AS/NZS 3003
AS/NZS 3003:2018 lists the kinds of rooms that are patient areas in Clause 2.2.4. A room on the list is wired as a body-protected area (or… - What do the B, BF and CF symbols on medical equipment mean?
Medical electrical equipment carries a symbol for how well the part that touches the patient (the applied part) is protected against… - AS/NZS 3003, 3551 and 3760: which test is which?
Three different standards get called “testing” in a practice, and they cover three different things. AS/NZS 3003 covers the electrical… - How much does a body-protected area cost?
There is no set price, and this site does not quote. What moves the cost is the number of rooms and outlets (each 10 mA RCD protects at… - Who can do the 12-month body-protected area test?
The standard says what the routine inspection and test covers and that it happens at intervals not exceeding 12 months. Who does it is set… - Landlord or tenant: who is responsible for the body-protected area?
Usually the practice. The electrical installation inside a tenancy is normally the tenant’s fit-out, and so is keeping it tested: the duty… - Were any 10 mA medical RCDs recalled?
Yes. On 29 October 2020 Schneider Electric recalled a range of Clipsal 10 mA RCD socket-outlets and service panels because a small… - Is the body-protected area test every 6 months or every 12 months?
Every 12 months at most. AS/NZS 3003:2018 requires routine inspection and testing at intervals not exceeding 12 months, which is why the… - Does every power point in a treatment room need its own circuit?
No. The rule is one room per circuit, not one outlet per circuit. The final sub-circuit that feeds a body-protected area serves that room… - Which edition of AS/NZS 3003 applies to my room?
The edition in force when the room was wired. AS/NZS 3003:2018 was published on 26 March 2018 and reissued with Amendment 1 in July 2019;… - Does a vet clinic need a body-protected area?
AS/NZS 3003 is written for patient areas in human health care: hospitals, medical and dental practices and the like, and the equipment… - Can a portable 10 mA RCD replace a body-protected area?
Not as a substitute for wiring the room. A body-protected area is a property of the installation: the 10 mA RCDs in the room, one circuit… - What is a Statement of Conformity for a body-protected area?
It is the document the installing electrician completes when a patient area is new, altered or repaired, based on the template in Appendix… - What does the 12-month body-protected area test involve?
A visit of an hour or so per room, with the room out of use while the RCDs are tripped. The tester starts with a look: every outlet, RCD,… - What will an accreditation surveyor ask about body-protected areas?
Evidence, mostly on paper. Australian surveyors work from the general practice and day procedure standards, which require safe, maintained… - Where do you buy the body-protected area sign, the 10 mA RCDs and the outlets?
From electrical wholesalers, and your electrician will normally supply them with the job. The parts have names worth knowing when you read… - What does RNZCGP accreditation ask for on body-protected areas?
Foundation Standard indicator 11.6 covers residual current devices and body-protected areas. If mains-powered medical equipment is used on… - No body-protected area yet? What goes in a transition plan (New Zealand)
Since RNZCGP rewrote Foundation Standard indicator 11.6 in October 2025, a practice using mains-powered equipment on patients outside a… - Does an electric examination bed need a body-protected area?
Not on its own, in New Zealand’s college guidance. RNZCGP’s electrical safety scenarios (June 2026) say a GP consult room with an electric… - Battery, plug-in and laptop ECGs: which need a body-protected area?
It turns on one thing: whether the patient is connected to something plugged into the wall while the leads are on. New Zealand’s RNZCGP… - How do I check a room on WorkSafe’s high-risk database?
In New Zealand, installation work for electrical medical devices is high-risk prescribed electrical work, and it is recorded on WorkSafe’s… - What if two electricians give different advice?
It happens, usually over whether a room is a patient area or how much of an existing room has to be upgraded. Ask each of them to explain…
Ask a question for the guide
Not answered above? Ask it here. A person reads every question. If it is one other practices or electricians ask too, we answer it as a page on this site and email you the link; if not, we reply to you directly. Nothing is published with your name on it.
Questions about whether a particular room complies get the same answer every time: that is for your practice, its clinicians and electrician to decide, and your state to sign off.
Rules in your state
Pick your state
See who certifies and inspects there.