Body-protected areas in Western Australia

Medical and dental room electrical rules in Western Australia

In Western Australia, the electrical contractor lodges a notice of completion for notifiable work with the network operator within 3 days, which triggers sample inspections, and gives you an electrical safety certificate within 28 days. Building and Energy publishes its own guidance on electrical work in medical centres, which says the owner or operator classifies the rooms and the electrician must confirm and document that before starting.

WA

Notice of completion and a safety certificate

Who certifiesThe electrical contractor, on an electrical safety certificate given to you within 28 days.
NotificationNotifiable work needs a notice of completion lodged with the network operator within 3 days of finishing.
InspectionNotices of completion trigger sample inspections of the work.
Regulator guidanceBuilding and Energy’s page on electrical work in medical centres (updated 21 September 2026) lists the common defects it finds: rooms wrongly identified, no commissioning records, 30 mA RCDs where 10 mA is required, missing signs.

Regulator: Building and Energy

What to do as the practice

  • Classify your rooms and give the electrician that in writing: Building and Energy says that is the owner or operator’s job, not the electrician’s.
  • Get the electrical safety certificate and the AS/NZS 3003 test results.
  • Book the 12-month routine test, and have the room tested before any alterations.

Check a room · Classification record template · Changing an existing room

Testing, everywhere

AS/NZS 3003:2018 (including Amendment 1:2019) requires routine inspection and testing of body-protected areas at intervals not exceeding 12 months. The date of the last test goes on the label on the green sign in the room. The room itself is built to the same rules in every state: the rules, one by one.

Work out when yours is due

If the regulator checks

Every notice of completion goes to the network operator, which inspects a sample of each electrician’s jobs, usually one in five, with the rate adjusted to the electrician’s record. Inspectors issue orders and notices of defect. Building and Energy, part of the Department of Local Government, Industry Regulation and Safety since July 2025, acts for the Director of Energy Safety.

WorkSafe WA expects workplace safety switches to be tested regularly by a competent person, with test records (other than daily checks) kept until the next test.

Have these ready

  • The electrical safety certificate for every job (your contractor keeps a copy for 5 years)
  • The AS/NZS 3003 test results, and a current date on each room’s label
  • Your classification record
  • Safety switch test records

Day-procedure clinics and private hospitals

Private hospitals and day procedure facilities are licensed by the Department of Health’s Licensing and Accreditation Regulatory Unit under the Private Hospitals and Health Services Act 1927. WA’s own Health Facility Guidelines for Engineering Services (2025 edition, in use from 2 February 2026) are the main design and compliance document for licensing, and include a section on electromedical protection systems.

WA Health: licensing of private healthcare facilities

Need an electrician in Western Australia?

Looking for listed electricians in Western Australia…

Ask us to find an electrician in Western Australia

Tell us about the job. We check licences and patient-area experience before recommending anyone, and we’ll send you what to ask whoever you use in the meantime.

Do you do this work in Western Australia?

Electricians and fit-out builders with AS/NZS 3003 experience can be listed here. Licence checked first, free while the directory is new.

Get listed

Listings are free and licence-checked. How listings work.

Sources for Western Australia

What this page relies on. Every link is re-read monthly; the footer shows when.

ActElectricity Act 1945 (WA)
RegulationElectricity (Licensing) Regulations 1991 (WA): notices of completion and electrical safety certificates
CertificateNotice of completion to the network operator within 3 days; electrical safety certificate to you within 28 days
Regulator guidance on patient areasBuilding and Energy publishes guidance on electrical work in medical centres (in its information for electrical licence holders, updated 21 September 2026): classification is the owner or operator’s responsibility, electricians must confirm and document it before work starts, and it lists the defects inspectors commonly find.
StandardAS/NZS 3003:2018 (including Amendment 1:2019), the same joint standard in every Australian state and territory and in New Zealand

Pages we read

Sources checked 1 November 2026. Rules change: always confirm with Building and Energy. Spotted something out of date? Tell us. Changes are logged on the Updates page.

Was this page useful?