Body-protected areas in Victoria

Medical and dental room electrical rules in Victoria

In Victoria, electrical installation work in a patient area is prescribed electrical work. Your electrician installs it, tests their own work and issues the Certificate of Electrical Safety, then an independent ‘M’ class licensed electrical inspector inspects and tests the room to AS/NZS 3003 and fits the test label before it’s connected to supply. The 12-month routine test is different: Energy Safe Victoria treats periodic testing that involves no installation work as outside the prescribed-work system, so the practice (or its electrician) organises it, and in practice it is usually carried out by an M class inspector, who knows the tests and fits the new label.

VIC

Two steps, two people

Who certifiesYour electrician completes and tests the work and issues a prescribed Certificate of Electrical Safety.
Independent inspectionYes. An ‘M’ class licensed electrical inspector (patient areas) inspects the work before it’s connected to supply. The inspector can’t be someone involved in installing it.
Testing at installTested to AS/NZS 3000 before it’s energised, then to AS/NZS 3003 after energising and before the room is put into service.
Your job as the practiceBefore work starts, give your electrician written notice of where your patient areas are and their boundaries.
Inspection timingEnergy Safe Victoria gives the electrician eight business days after completing the work to have it inspected by the licensed electrical inspector.
A recalled RCD to know aboutIn October 2020 Schneider Electric recalled a range of Clipsal 10 mA RCD outlets and panels with date codes from 1 July 2017 to 15 October 2020, because some trip above 10 mA (part numbers beginning 2025RC10, 2031RC10, 2031VRC10, C2025RC10, ML2025RC10, ML2031RC10 and ML2031VRC10). A room fitted out in those years may still have them: ask at the next test. Replacing a single RCD or outlet like for like is non-prescribed work in Victoria, certified on a non-prescribed certificate after testing.

Regulator: Energy Safe Victoria

What to do as the practice

  • Tell your electrician in writing which rooms are patient areas, before any work starts.
  • Ask who the ‘M’ class inspector will be and when they’re booked.
  • Keep the Certificate of Electrical Safety and the test records with your compliance files.
  • Book the 12-month routine test, and have the room tested before any alterations.
  • If your rooms were fitted out between mid-2017 and late 2020, ask your tester to check the 10 mA RCD part numbers against the 2020 Schneider recall.

Check a room · Classification record template · Changing an existing room

Testing, everywhere

AS/NZS 3003:2018 (including Amendment 1:2019) requires routine inspection and testing of body-protected areas at intervals not exceeding 12 months. The date of the last test goes on the label on the green sign in the room. The room itself is built to the same rules in every state: the rules, one by one.

Work out when yours is due

If the regulator checks

Energy Safe Victoria can audit any job done under a Certificate of Electrical Safety: an auditor visits, looks at the work and tests it. The audit is free and you can decline it. If the work doesn’t comply, the electrician has to come back and fix it at no cost to you, and Energy Safe can issue an improvement notice with a deadline.

For your workplace, WorkSafe Victoria expects electrical equipment to be kept safe and records kept of any testing. For low-risk areas its guidance suggests pressing the test button on fixed safety switches every 6 months and a trip-time test every 2 years; the room’s 12-month AS/NZS 3003 test covers its own RCDs.

Have these ready

  • The Certificate of Electrical Safety for every job in the rooms (your electrician keeps their copy for 3 years)
  • The inspector’s AS/NZS 3003 test results, and a current date on each room’s label
  • Your written notice of the patient areas and your classification record
  • Records of safety switch and appliance testing

Day-procedure clinics and private hospitals

Private hospitals and day procedure centres are registered by the Department of Health under the Health Services Act 1988 and the Health Services (Health Service Establishments) Regulations 2024. You need an approval in principle before building, and the Department inspects the premises against the Australasian Health Facility Guidelines before registering it. Its guideline for alterations lists body-protection and cardiac-protection electrical certification among the certificates it asks for.

Department of Health: day procedure centres

Need an electrician in Victoria?

LND Group is the site publisher’s own business. How listings work.

Sources for Victoria

What this page relies on. Every link is re-read monthly; the footer shows when.

ActElectricity Safety Act 1998 (Vic)
RegulationElectricity Safety (General) Regulations 2019 (Vic), including regulation 249 on patient areas
CertificateCertificate of Electrical Safety (prescribed), plus inspection by a Class M licensed electrical inspector before connection
Regulator guidance on patient areasEnergy Safe Victoria publishes patient-area guidance: its electrical installation FAQs say patient-area work is prescribed and must be inspected by an M class inspector, and set out the written-notice duty.
StandardAS/NZS 3003:2018 (including Amendment 1:2019), the same joint standard in every Australian state and territory and in New Zealand