Body-protected area fit-out checklist
What to decide before the walls close. Print it for your builder and electrician.
- Room use. Every room listed with how it will be used, and its classification agreed with clinicians and the electrician, on the classification record (bpea.com.au/classification-record), given to the electrician in writing.
- Equipment. The equipment list with supplier spec sheets: chairs, imaging, sterilisers, lasers, monitoring.
- Switchboard and RCDs. Capacity for the new circuits, and each room’s 10 mA RCDs located in the room: a wall-mounted RCD plate or a small switchboard for that room.
- Dedicated circuits. Separate circuits for chairs, imaging and sterilisers to each supplier’s spec.
- Outlets and signage. Protected outlets identified, the green sign inside each room, and a cleaners’ outlet on its own circuit within 15 metres of the room.
- Sign-off booked. Your state’s certificate, and any inspection or audit, booked into the builder’s programme.
- Handover pack. Certificates, AS/NZS 3003 test results and the next test date, kept with your compliance files.
- First retest. Booked within 12 months of handover.