bpea.com.au
Home › The rules

The rules, one by one

What AS/NZS 3003 requires in a body-protected area

Every rule that applies to an ordinary practice room, in plain English, with where it sits in AS/NZS 3003:2018 (including Amendment 1:2019). For practice managers who want to understand the quote, and electricians who want the clause.

In one minute

  • The practice decides which rooms are patient areas, and writes it down.
  • Every outlet in the room is on a 10 mA RCD that sits in the room: up to 12 points each, nothing at 30 mA behind it.
  • Each outlet shows an amber light and the number of its RCD. White for normal supply, beige for cleaning.
  • No standard outlets within 2 m of the door frame: only a cleaners’ outlet or a 10 mA protected one.
  • A beige cleaners’ outlet on its own circuit and RCD, within 15 m.
  • The green sign inside the room, top edge at 2 m, with the test label.
  • Tested before the first patient and at least every 12 months. No alterations without a current test.

How to read this page

These are our own words, not the standard’s: the text, figures and tables of AS/NZS 3003 are copyright and the wording that binds is in the standard itself, sold by Standards Australia and Standards New Zealand. Section numbers come from the standard’s published contents; clause numbers are cross-checked against its preface and the published guides to it. If your copy says otherwise, tell us.

The numbers at a glance

Every figure the standard turns on for a practice room, with where it sits. The detail is further down the page. The printable version is the quick reference (PDF), which adds the pre-inspection list and the 12-month test.

FigureWhat it isWhere in AS/NZS 3003:2018
10 mAThe trip rating of every RCD protecting a patient-area outlet or hard-wired patient equipment. Type 1, double-pole (it switches active and neutral), tripping within 40 ms.Clause 2.8.1
12 pointsThe most one RCD may protect. A point is a socket-outlet or a piece of hard-wired equipment, and a double outlet is two points.Clause 2.8.3(a)
1 room per circuitEach final sub-circuit, and each RCD, serves one room (with its ensuite) and nothing else.Clauses 2.4.1.1, 2.8.3(b)
0 RCDs upstreamNothing backs up the room’s 10 mA RCD: no 30 mA RCD at the switchboard on that circuit.Clause 2.8.2
2.0 mReadily accessible means reachable quickly, without climbing or moving anything, and no higher than 2 m. RCDs and the outlets staff use sit below it; the sign’s top edge sits at it.Clause 1.5 (definitions); Section 2.6; Clause 2.12.2
500 mmThe least distance between the room’s RCD and a light switch.Section 2.6
1200 mm and 250 mmAn RCD is not mounted under a shelf or structure lower than 1200 mm that projects more than 250 mm from the wall.Section 2.6
2.0 to 2.3 mOutlets in this band are out of reach: still 10 mA protected, with a readily accessible double-pole isolating switch below 2 m.Clauses 2.4.3.2.2, 2.7.2
Above 2.3 mPermanently mounted non-medical equipment, an air conditioner for instance, is outside the patient-area rules, as long as its outlet is not looped with the protected outlets below.Clause 2.4.3.2.2 (exception)
2 m from the door frameNo standard outlets outside the room within this distance, measured in a straight line: a cleaners’ outlet or a 10 mA protected outlet with its own RCD only. Behind a locked door does not count.Clause 2.4.3.2.2(b)
15 mThe furthest a cleaners’ outlet can be from the area it serves.Clause 2.7.3.1
2.0 kWNew fixed equipment at or above this rating brings the whole patient area up to the current standard.Clause 6.2.5.2
10%If added outlets increase a patient area’s total by more than 10%, every outlet in it gets the current colour coding.Clause 6.2.4
12 monthsThe longest gap between routine inspections and tests. Alterations go ahead only with a test in the previous 12 months.Section 8; Clause 6.2.3
1.5 mm, 2.0 mm, 5.0 mmMinimum lettering heights: 1.5 mm for switchboard and circuit-breaker identification, 2.0 mm for RCD and outlet identification, 5.0 mm for “Cleaning Purposes Only”.Section 2.12; Clause 2.7.4.3.1(d)
200 × 90 mmThe size the green sign is sold in. The standard sets the symbol and the position; the size comes from the sign makers.Clause 2.12.2; Section 7
50 mmUnprotected supply cables to an RCD concealed within 50 mm of the surface get an earthed metal screen or armour, as the Wiring Rules describe.Clause 2.4.2; AS/NZS 3000 Clause 3.9.4.4

Heights on the wall

The wall opposite the door, seen from inside the room. The numbers match the list.

Floor2.0 m2.3 m2.0 to 2.3 m: out of reach, still protectedDoorBenchRCD≥ 500 mmBODY-PROTECTED ELECTRICAL AREAtop edge at 2.0 mscreenAir conditioner, fixed123456
  1. 1Protected outlets above the bench, each with the amber indicator and marked with the RCD that protects it.
  2. 2The room’s RCD: no higher than 2 metres, above the bench, readily accessible, labelled with its switchboard, circuit breaker and number.
  3. 3At least 500 mm from the light switch by the door, so nobody trips the room reaching for the light.
  4. 4The green sign, top edge at 2 metres, inside the room, with the test label on it.
  5. 5Between 2.0 and 2.3 metres: an outlet for a wall screen is treated as out of reach, but it is still RCD protected, with an isolating switch someone can reach.
  6. 6Above 2.3 metres: permanently mounted non-medical equipment such as an air conditioner is exempt from the patient-area rules.

The 2-metre rule at the door

The entrance from above: the treatment room with a locked store off it, and the corridor outside.

CorridorOfficeTreatment roomStore (locked)BODY-PROTECTED ELECTRICAL AREA2 m fromthe door frame1234
  1. 1The door frame. The 2 metres is measured from here in a straight line, not along the skirting.
  2. 2Within 2 metres of the door frame: no standard outlets. This one is the beige cleaners’ outlet, on its own circuit and its own 10 mA RCD. A protected outlet with its own 10 mA RCD beside it would also do; it can’t go on the room’s RCD, which only covers the room.
  3. 3Further down the corridor, more than 2 metres from the door frame: a standard outlet is fine.
  4. 4A store off the room, behind a locked door: it can have standard outlets, even within 2 metres of its door frame. The same goes for anything reached only through a second doorway.

The whole room from above, with the chair, the RCD and the cleaners’ outlet down the corridor, is on the home page.

Deciding and recording which rooms are patient areas

The practice decides, room by room

A room is a patient area if mains-powered medical equipment will be applied to a patient in it. The decision is based on the procedures carried out there, not on what the room is called, and it is the practice’s (the ‘responsible organisation’), with input from clinicians, equipment suppliers and the electrician. The electrician does not classify rooms. The standard also lists rooms that are always patient areas, dental surgeries among them, and any patient area that is not cardiac-protected has to be body-protected: there is no third, lesser option.

Section 2.2; Clause 2.2.4 (rooms that are patient areas); Appendix A (planning)

Body-protected or cardiac-protected follows the equipment

Equipment that touches the body (a dental handpiece, an ECG, an ultrasound probe, a laser) leads to a body-protected area. Equipment that can make a direct electrical connection to the heart (cardiac catheters, some theatre and intensive-care equipment) leads to cardiac-protected. Almost every private practice room is body-protected. The standard points practices to AS/NZS 2500 for how to make the call. The equipment label helps: a Type B symbol (a person) or Type BF (the person in a box) points to body-protected; Type CF (a heart in a box), which can connect to the heart, points to cardiac-protected.

Clause 1.2 (refers to AS/NZS 2500); Section 2.2; Appendix A

Write it down and keep it on the premises

The practice must keep a written record of every patient area and its classification, of every room it has decided is not a patient area and why, and of every alteration or change of use, available for inspection at the premises. Victoria’s regulations and Western Australia’s guidance both expect this to be handed to the electrician in writing before work starts. The classification record template on this site is laid out for exactly that.

Clause 2.2.1 (documentation); Section 2.14 (additional documentation)

Boundaries are walls and doors

A patient area runs to its full-height walls and doors. Curtains, partitions, nib walls, benches and screens do not make a boundary, and a staff station inside the area is part of it. A patient ensuite, bathroom or toilet opening off the room is part of the area too.

Clause 2.2.2 (boundaries); Clause 2.2.4 (ensuites)

The standard’s own list of patient areas

Clause 2.2.4 lists the kinds of rooms that are patient areas: accident and emergency, anaesthetic and resuscitation bays, theatres and recovery, wards and high dependency, nurseries, delivery suites, dental surgeries, treatment rooms, doctors’ consulting rooms, outpatient examination rooms, dermatology, imaging and ultrasound, endoscopy, audiometry, blood collection, plaster rooms, respiratory function labs, stress test rooms, plasmapheresis, and allied health rooms such as chiropractic, physiotherapy, optometry and naturopathy. Being on the list is why many electricians treat every consult room as one. Under the 2018 edition the classification follows the procedures done in the room, so a consult room where no mains-powered equipment is applied to a patient can be recorded as not a patient area. That call is the practice’s, and it goes in the classification record with the reason.

Clause 2.2.4

Circuits and supply

Each room has its own circuits

The final sub-circuits that feed a body-protected area serve that room (and its ensuite) only. Outlets are not looped from one treatment room to the next, and one RCD never feeds points in two different rooms, so an ensuite sharing the room’s circuit still gets its own RCD. A fault or a trip in one surgery never takes out the room beside it. The chair, imaging equipment and anything else the supplier specifies get dedicated circuits of their own.

Clause 2.4.1.1 (one room per sub-circuit); Clause 2.8.3(b) (one room per RCD)

USB and other charging outlets are protected too

Extra-low-voltage charging sockets built into wall plates, USB included, count. In a patient area they are RCD protected like the mains outlets around them.

Clause 2.4.3.1.2 (ELV charging sockets, including USB)

Hard-wired equipment is protected and testable

Permanently connected equipment applied to the patient (with electrodes, instruments that enter the body, or liquid in contact with the patient) still needs 10 mA double-pole protection, and gets a white round-pin ‘test only’ outlet so the protection can be tested without disconnecting the equipment.

Clause 2.4.3.3 (protection); Clause 2.8.6 (the test outlet)

The cables feeding an RCD are protected mechanically

The supply cables running to an RCD sit before the 10 mA protection. Where they are concealed within 50 mm of the wall surface they get an earthed metal screen or armour, in the ways the Wiring Rules set out. A 30 mA RCD upstream is not a substitute, and would break the no-RCD-upstream rule anyway.

Clause 2.4.2; AS/NZS 3000 Clause 3.9.4.4

The RCDs (safety switches)

10 mA, Type 1, double-pole, in the room

Every outlet in a body-protected area is protected by a 10 mA Type 1 RCD that switches both active and neutral and trips within 40 milliseconds. The RCDs live in the room, on a wall plate or a small switchboard for that room, not back at the main switchboard.

Clause 2.8.1 (type and rating)

No more than 12 points on one RCD

One RCD can protect up to 12 points. A point is a socket-outlet or a piece of hard-wired equipment, so fixed equipment counts against the twelve as well. A room with more points simply has more RCDs. This is the rule people misquote as ‘12 power points’.

Clause 2.8.3(a)

Nothing upstream at 30 mA

The 10 mA RCD in the room must not be backed up by another RCD, such as an ordinary 30 mA RCD on the switchboard. Two RCDs in series means the wrong one can trip, and a trip at the switchboard takes the room out from somewhere nobody in the room can reach.

Clause 2.8.2

Where the RCD goes on the wall

Readily accessible to staff and visible: no higher than 2 metres, not under a bench or inside a cupboard, above the bench if it is on the bench wall, and at least 500 mm from a light switch near the door so nobody turns the room off reaching for the light. Each RCD is labelled with the switchboard and circuit breaker that feed it and its own number, so the ‘From RCD 2’ on an outlet means something. “Readily accessible” has a definition: reachable quickly, without climbing onto or over anything or moving obstructions, and no more than 2 m above the floor. The same section rules out mounting an RCD under a shelf or projection lower than 1200 mm that sticks out more than 250 mm from the wall. Two exceptions: the cleaners’ RCD may sit away from its outlet, typically at the switchboard, and an ensuite’s RCD may go in the vanity cupboard.

Section 2.6 and Table 2.1 (access to controls and indicators); Clause 2.8.5 (RCD labelling)

Socket-outlets

Every outlet protected, and showing it

Each outlet carries a single amber (or yellow or orange) indicator light that shows the supply is on, and is marked as RCD protected with the number of the RCD that protects it. The outlet does not carry the switchboard or circuit breaker label; that goes on the RCD. USB and other low-voltage charging outlets don’t need the light.

Clause 2.7.4.1 (labelling and indicator)

Colours mean supply

White outlets are the normal supply. Red is essential supply (backed by a generator), dark blue is uninterruptible supply, and beige is the cleaners’ outlet, marked for cleaning purposes only. A practice without a generator or UPS will only ever see white and beige.

Clause 2.7.4.3 (colours)

The 2-metre rule at the door

Outside the room, within 2 metres of the door frame, there are no standard outlets. An outlet there has to be on 10 mA RCD protection: either the beige cleaners’ outlet, or a protected outlet with its own 10 mA RCD mounted beside it, because the room’s RCDs only cover the room. Measure in a straight line from the door frame, not along the wall. Outlets behind a locked door, such as a store off the room, or reached only through a second doorway, are excluded; so is anything that needs a key or tool to get at. More than 2 metres away, standard outlets are fine.

Clause 2.4.3.2.2(b)

Height zones: 2.0 m and 2.3 m

Outlets above 2.0 metres are treated as out of reach, so a screen outlet high on the wall need not be accessible, but it is still protected, and an outlet nobody can reach gets a double-pole isolating switch that they can, below 2 metres. Above 2.3 metres an outlet is exempt from the patient-area rules only if it supplies permanently mounted non-medical equipment, such as an air conditioner, and is not looped with the protected outlets below it.

Clause 2.4.3.2.2 (the exception above 2.3 m); Clause 2.7.2 (isolation for outlets out of reach)

The cleaners’ outlet

A beige outlet on its own circuit, protected by its own 10 mA RCD that protects cleaners’ outlets only, so a vacuum cleaner can never trip the room or be plugged into a patient outlet. It can be inside the area or within 15 metres of it, and one can serve several rooms. MRI rooms are the exception.

Clause 2.4.1.3 (its own circuit); Clause 2.7.3.1 (within 15 m)

Each outlet individually switched, and showing when it is on

Every socket-outlet in the area has its own switch, and the switch shows it is on with a red marking or a red light. The amber indicator says supply is present; the red says the outlet is switched on. A quote with unswitched outlets or shared switches is not to the standard.

Clauses 2.7.5, 2.7.4.2

Isolating fixed equipment

An isolator within reach for equipment you cannot unplug

A dental chair’s supply usually sits under the base where nobody can reach the plug. Equipment like that gets an isolating switch within reach that breaks all live conductors, so it can be shut off for servicing or in an emergency.

Section 2.10 (isolation switches); and the Wiring Rules, AS/NZS 3000

Earthing

Body-protected earthing is the Wiring Rules, done carefully

A body-protected area’s earthing follows the Wiring Rules. The heavy equipotential bonding of every metal object in the room, with earth terminals and test points, is a cardiac-protected requirement in Section 4. Some regulator guidance lists bonding under body-protected areas too, so expect your electrician to earth or bond metallic plumbing and fixed metal fittings within the patient’s reach, and ask which section they are working to.

Clause 3.2 (body-protected: earthing to AS/NZS 3000); Section 4.4 (cardiac-protected)

The sign and the labels

The green sign, top edge at 2 metres

Every body-protected area has the green sign with the body-protected symbol, on a wall inside the room where it is seen on entering, with its top edge 2 metres above the floor. The signs sold for it are 200 mm wide by 90 mm high. It carries the test label showing when the room was last tested and by whom.

Clause 2.12.2 (position); Section 7.2 (the sign)

Labels that match

The RCDs, outlets and switchboard labels cross-reference each other: the outlet names its RCD, the RCD names its circuit breaker and switchboard. Labels are fixed so they can’t come off with a clip-on cover, and after alterations they are updated so the record is still true. The lettering has minimum heights: 1.5 mm for the switchboard and circuit-breaker identification, 2.0 mm for the RCD and outlet identification, 5.0 mm for “Cleaning Purposes Only”. The outlet marking reads “RCD Protected” and “From RCD X”, with the word FROM in it, and carries no switchboard reference. Labels are not fixed to a removable surround unless the same identification is also on the body of the device.

Section 2.12 (identification); Clause 2.8.5; Section 6.4 (identification after alterations)

Testing, new and routine

Tested and verified before the first patient

New or altered work is inspected and tested to the standard before the area is used on patients: RCD trip current and time, earthing, polarity, the labelling and the sign. The standard provides a commissioning checklist and a statement-of-conformity form for this. Who signs it off, and whether an independent inspector is involved, depends on your state. The installer also completes a Statement of Conformity (the template is Appendix C): whether the work is a new area, an alteration or a repair; body-protected or cardiac-protected; the premises, the room, a description of the work and its date; that the tests passed and the work conforms to the Wiring Rules; whether outlet numbers and likely loads were agreed with clinical staff; and the installer’s name, company and licence number. Ask for a copy and keep it with the classification record.

Section 2.13 (testing and verification); Appendix B (commissioning checklist); Appendix C (statement of conformity)

Routine inspection and testing, at least every 12 months

Every body-protected area is inspected and tested at intervals not exceeding 12 months, using the standard’s routine checklist: the RCDs trip as they should, the earthing is intact, outlets and labels are in order, the sign is there. The date goes on the test label. Alterations should not go ahead unless the area has had its routine test in the previous 12 months. On the day the tester looks at every outlet, RCD, isolator and the sign, confirms the labels still match, measures earth continuity on the outlets and fixed equipment, checks polarity, trips each 10 mA RCD and records its trip current, trip time and indicators, and writes up any fault. A new test label goes on the sign once the room passes. The full list is under the pre-inspection list below.

Section 8 (routine inspection and testing; 8.2 for body-protected areas); Appendix E (routine checklist); Clause 6.2.3 (alterations)

Alterations and repairs

Changing anything in the room has rules of its own

Adding outlets, moving the chair, installing fixed equipment of 2.0 kW or more, repairing a fault and changing a room’s use each trigger specific requirements, including bringing an unsigned patient area up to the standard before or during the work. They have their own page.

Section 6: 6.2 alterations, 6.3 repairs, 6.4 identification

More than 10% more outlets, and the label afterwards

If added outlets increase a patient area’s total by more than 10%, every outlet in the area is brought to the current colour coding, not just the new ones. After any alteration, addition or repair, a label goes below the routine test label showing that alterations occurred, with the report number, date, who tested it, their organisation and contact details. The routine test label stays.

Clauses 6.2.4, 6.4

For electricians

Before you certify or book the inspector

What an inspector or certifier will look at, in the order you’d walk the room. Our own list, not the standard’s Appendix B checklist; use that for the record.

  • The practice’s classification of each room, and the boundaries, in writing before you start. Clause 2.2.1
  • Each final sub-circuit serves one room and its ensuite only; no RCD feeds points in two rooms. Clauses 2.4.1.1, 2.8.3(b)
  • 10 mA Type 1 double-pole RCDs, no more than 12 points each, none backed up by another RCD. Clauses 2.8.1, 2.8.2, 2.8.3(a)
  • RCDs readily accessible and visible: 2 m or lower, not under benches or in cupboards, 500 mm or more from the light switch. Section 2.6, Table 2.1
  • RCDs labelled with their switchboard, circuit breaker and number; outlets marked RCD protected and ‘From RCD X’, with no switchboard label on the outlet. Clauses 2.8.5, 2.7.4.1
  • Outlet colours right, amber indicators on every mains outlet, cleaners’ outlets beige and marked for cleaning only. Clauses 2.7.4.1, 2.7.4.3
  • No standard outlets within 2 m of the door frame, unless behind a locked door: only a cleaners’ outlet, or a 10 mA protected outlet with its own RCD beside it. Clause 2.4.3.2.2(b)
  • Any outlet that isn’t readily accessible has a readily accessible double-pole isolator below 2 m. Clause 2.7.2
  • USB and other ELV charging outlets RCD protected. Clause 2.4.3.1.2
  • Hard-wired patient equipment on 10 mA protection with a white test-only outlet; fixed equipment with an unreachable plug has an isolator. Clauses 2.4.3.3, 2.8.6; Section 2.10
  • Cleaners’ circuit dedicated, on its own RCD, outlet within 15 m of the area. Clauses 2.4.1.3, 2.7.3.1
  • Green sign fitted inside, top edge at 2 m, ready for the test label. Clause 2.12.2; Section 7
  • Earthing to the Wiring Rules. Clause 3.2
  • An RCD tester that can do the AS/NZS 3003:2018 tests. Energy Safe Victoria warns that some testers with 0° and 180° switches can’t. Energy Safe Victoria
  • Tested to AS/NZS 3000 before energising and to AS/NZS 3003 after, before the room goes into service, with results on the commissioning checklist and statement of conformity. Section 2.13; Appendices B and C
  • Every outlet individually switched, with the red on-indication. Clauses 2.7.5, 2.7.4.2
  • Lettering heights: 1.5 mm board and breaker IDs, 2.0 mm RCD and outlet IDs, 5.0 mm Cleaning Purposes Only; the word FROM on outlet labels; nothing on a removable surround alone. Section 2.12; Clauses 2.7.4.1, 2.12.1
  • Supply cables to the RCDs screened or armoured where concealed within 50 mm of the surface. Clause 2.4.2
  • After an alteration: outlets recoloured if the count rose by more than 10%, and the alteration label fitted under the test label. Clauses 6.2.4, 6.4
  • Statement of Conformity completed and a copy left with the practice. Appendix C

What the 12-month routine test covers

Our plain-English version of the standard’s routine checklist (Appendix E).

  • A look at every outlet, RCD, isolator and the sign: damage, the right colours, indicators working, no more than 12 points on an RCD.
  • Labels still true: each outlet names its RCD, each RCD names its circuit breaker and switchboard, the cleaners’ outlet is marked for cleaning only.
  • Every outlet works and is individually switched; polarity correct.
  • Earth continuity measured on every outlet and on fixed equipment in the area.
  • Every 10 mA RCD tripped with a tester that can do the AS/NZS 3003 tests: trip current and trip time within limits, both poles opening, the test button and indicator working.
  • Where an isolated supply with a line isolation monitor is fitted (rare outside hospitals), the monitor and its alarm.
  • Faults and observations recorded; anything failed fixed before the room is used again.
  • A new test label on the sign, dated and signed, the report to the practice, the classification record updated.

Changing an existing room?

Moving the chair, adding outlets, new fixed equipment, a room with no sign, an expired test label: each has its own rule in Section 6.

Alterations and repairs

Common questions about the rules

How many power points can be on one RCD in a body-protected area?

Twelve points. A point is a socket-outlet or a piece of hard-wired equipment, so fixed equipment counts too. Rooms with more points have more RCDs. (AS/NZS 3003:2018, Clause 2.8.3(a).)

How high can the RCD be mounted in a treatment room?

No higher than 2 metres, readily accessible and visible, not under a bench or in a cupboard, and at least 500 mm from a light switch near the door. (AS/NZS 3003:2018, Section 2.6 and Table 2.1.)

What colour are the outlets in a body-protected area?

White for normal supply, red for essential supply, dark blue for UPS supply and beige for the cleaners’ outlet. Each mains outlet has an amber indicator and is marked with the RCD that protects it. (AS/NZS 3003:2018, Clauses 2.7.4.1 and 2.7.4.3.)

Do outlets outside the room need to be protected?

Yes, if they are within 2 metres of the door frame, measured in a straight line, and can be got at without a key or tool. There should be no standard outlets there: use a cleaners’ outlet, or a 10 mA protected outlet with its own RCD beside it, since the room’s RCDs only cover the room. Outlets behind a locked door or through a second doorway are excluded. (AS/NZS 3003:2018, Clause 2.4.3.2.2(b).)

How big is the body-protected area sign and where does it go?

The signs sold for it are 200 mm by 90 mm. It goes on a wall inside the room where it is seen on entering, with its top edge 2 metres above the floor, and carries the test label. (AS/NZS 3003:2018, Clause 2.12.2 and Section 7.2.)

Does a body-protected area need equipotential bonding?

Body-protected earthing follows the Wiring Rules (Clause 3.2); full equipotential bonding of everything in the room is a cardiac-protected requirement in Section 4. Metallic plumbing and fixed metal within the patient’s reach is still earthed or bonded. Ask your electrician which section applies.

Can I alter a treatment room if its test label has expired?

Not until it has been tested: alterations should only go ahead if the area has had its routine test in the previous 12 months, and repairs need a current test sticker. (AS/NZS 3003:2018, Clauses 6.2.3 and 6.3.2.)

Is the body-protected area test every 6 months or every 12 months?

Twelve months is the limit, not a minimum: the standard sets routine inspection and testing at intervals not exceeding 12 months. Some testers offer 6-monthly visits, and New Zealand’s practice accreditation standard asks the practice to press the RCD test buttons itself every 6 months and keep a record. Neither replaces the 12-month test. (AS/NZS 3003:2018, Section 8.)

Does a double power point count as one point or two?

Two. The limit of 12 points per RCD counts each socket, so six double outlets fill an RCD. Hard-wired equipment counts as well. (AS/NZS 3003:2018, Clause 2.8.3(a).)

Does every power point in a treatment room need its own circuit?

No. The rule is one room per circuit, not one outlet per circuit: the final sub-circuit serves that room and its ensuite only, and the room’s outlets share it behind the 10 mA RCDs. The chair, imaging equipment and other large items get dedicated circuits because of their load, not because every outlet must. (AS/NZS 3003:2018, Clause 2.4.1.1.)

Sign-off is set by your state

The standard says what the room needs. Who certifies and inspects it is state law.

Need an electrician who works to this?

VictoriaLND Group, MelbourneMedical and commercial electricians. Installation, with the M class inspection and 12-month testing organised.Visit LND Group →REC 30162

Other states and New Zealand

Pick your state for its rules and the electricians listed there, or ask us to find one. Electricians and builders can get listed.

LND Group is the site publisher’s own business. How listings work.

Was this page useful?