bpea.com.au
Home › By state › Queensland

Body-protected areas in Queensland

Medical and dental room electrical rules in Queensland

In Queensland, the licensed electrical contractor tests the installation work and gives you a certificate of testing and compliance confirming it’s electrically safe and meets the wiring rules and any other applicable standard, which for a patient area includes AS/NZS 3003. The Electrical Safety Regulation 2026 replaced the 2013 regulation on 1 September 2026 without changing this.

QLD

Your contractor tests and certifies

Who certifiesThe licensed electrical contractor, on a ‘certificate of testing and compliance’ for electrical installation work.
RecordsThe contractor must keep a copy of the certificate for five years. Keep yours with your compliance files.
Independent inspectionNone specific to patient areas. The Electrical Safety Office inspects and audits; Victoria’s separate prescribed inspection is specific to Victoria.
StandardAS/NZS 3003 applies to the patient areas themselves, as it does across Australia.

Regulator: Electrical Safety Office (WorkSafe Queensland)

What to do as the practice

  • Tell your electrician which rooms are patient areas and how each will be used.
  • Get the certificate of testing and compliance and the AS/NZS 3003 test results at handover.
  • Book the 12-month routine test, and have the room tested before any alterations.

Check a room · Classification record template · Changing an existing room

Testing, everywhere

AS/NZS 3003:2018 (including Amendment 1:2019) requires routine inspection and testing of body-protected areas at intervals not exceeding 12 months. The date of the last test goes on the label on the green sign in the room. The room itself is built to the same rules in every state: the rules, one by one.

Work out when yours is due

If the regulator checks

Electrical Safety Office and Workplace Health and Safety Queensland inspectors visit workplaces in campaigns and after complaints, and can ask to see documents. Anything that can’t be fixed on the spot gets a notice to remedy, and an electrician who does defective work can have their licence conditioned, suspended or cancelled.

The Electrical Safety Regulation 2026 also sets safety switch testing for workplaces: for office work, fixed safety switches get a push-button test every 6 months and an operating-time test every 2 years.

Have these ready

  • The certificate of testing and compliance for every job (your contractor keeps a copy for 5 years)
  • The AS/NZS 3003 test results, and a current date on each room’s label
  • Your classification record
  • Safety switch test records and test tags

Day-procedure clinics and private hospitals

Private hospitals and day hospitals are licensed by the chief health officer under the Private Health Facilities Act 1999, through Queensland Health, which also reviews the building plans. Queensland’s building code part for these facilities (QDC MP 5.5, 2008) requires electrical installations to AS 3003 and sets minimum outlet numbers, such as 6 body-protected outlets in a procedure area. It still cites the 1999 edition of the standard.

Queensland Health: a new private hospital or day facility

Need an electrician in Queensland?

Looking for listed electricians in Queensland…

Ask us to find an electrician in Queensland

Tell us about the job. We check licences and patient-area experience before recommending anyone, and we’ll send you what to ask whoever you use in the meantime.

Do you do this work in Queensland?

Electricians and fit-out builders with AS/NZS 3003 experience can be listed here. Licence checked first, free while the directory is new.

Get listed

Listings are free and licence-checked. How listings work.

Sources for Queensland

What this page relies on. Every link is re-read monthly; the footer shows when.

ActElectrical Safety Act 2002 (Qld)
RegulationElectrical Safety Regulation 2026 (Qld), in force from 1 September 2026
CertificateCertificate of testing and compliance for electrical installation work, from the licensed contractor
Regulator guidance on patient areasThe Electrical Safety Office publishes no guidance specific to patient areas. Its testing guide notes that AS/NZS 3003 installations have additional testing requirements.
StandardAS/NZS 3003:2018 (including Amendment 1:2019), the same joint standard in every Australian state and territory and in New Zealand

Pages we read

Sources checked 1 November 2026. Rules change: always confirm with Electrical Safety Office (WorkSafe Queensland). Spotted something out of date? Tell us. Changes are logged on the Updates page.

Was this page useful?